Characteristics of IT system distribution cabinet TR-VITC
- Internal components
- Isolating transformer (3150 to 8000 VA)
- Changeover module with voltage monitoring 65/80 A
- IT system monitoring
- Two-pole circuit breakers B16A per circuit for 6 circuits
- Customers can save time and money as the distribution cabinets are supplied prewired
- Covering of sheet-steel according to DIN VDE 0100-710: 2002-11 para. 710.51.2.2
Usages of IT system distribution cabinet TR-VITC
- socket-outlet circuits for medical electrical equipment and
- operating theatre luminaires circuits and similar lighting supplied with nominal voltages exceeding AC 25 V or DC 60 V, the protective measure ”Protection by insulation monitoring with indication in the IT system” is mandatory. Furthermore, a changeover module is required to change over automatically from the safety power supply source to a second supply source in case of failure.
No accessories available
Variants of IT system distribution cabinet TR-VITC
Ordering information
| Type | Nominal power | Weight | Power consumption | Art. No. |
|---|---|---|---|---|
| TR-VITC-3150 | 3150 VA | 130 kg | 248 W | on request |
| TR-VITC-4000 | 4000 VA | 143 kg | 234 W | on request |
| TR-VITC-5000 | 5000 VA | 145 kg | 275 W | on request |
| TR-VITC-6300 | 6300 VA | 150 kg | 314 W | on request |
| TR-VITC-8000 | 8000 VA | 160 kg | 350 W | on request |
Other versions on request