Changeover and monitoring modules for group 2 medical locations
Solutions for the power supply of group 2 medical locations, e.g. operating theatre rooms, intensive care units. Changeover and monitoring modules for use in accordance with DIN VDE 0100-710: 2002-11 para. 710.537.6.2 “Distributon boards for the power supply of group 2 medical locations”.
UFC107E
The factory-made modules of the UFC107E series are used to change over (t ≤ 0.5 s) between two supply sources (AV/SV resp. SV/UPS) and for IT system monitoring in medical locations. The UFC107E features an insulation fault location system to localize insulation faults in 6, 12, 18 or 24 outgoing circuits during operation. Each outgoing circuit has a two-pole circuit breaker. Status indication and alarm texts on the alarm indicator and operator units takes place via bus technology. The module is suitable for mounting onto all common DIN rail systems (equipment racks have to be provided by the customer).
The factory-made modules of the UMC107E series are used to change over (t ≤ 0.5 s) between two supply sources (AV/SV resp. SV/UPS) and for IT system monitoring in medical locations. Status indication and alarm texts on the alarm indicator and operator units takes place via BMS bus. The module is suitable for mounting onto all common DIN rail systems (equipment racks have to be provided by the customer).
The factory-made modules of the LFC107E series are used to monitor IT systems in medical locations. The LFC107E features an insulation fault location system to localize insulation faults in 6, 12, 18 or 24 outgoing circuits during operation. Each outgoing circuit has a two-pole circuit breaker. Status indication and alarm texts on the alarm indicator and operator units takes place via bus technology. The module is suitable for mounting onto all common DIN rail systems (equipment racks have to be provided by the customer).
The factory-made modules of the LTIC107 series are designed for monitoring single-phase (LTIC107E) or three-phase (LTIC107D) IT systems in medical locations. Status indication and alarm texts on the alarm indicator and operator units takes place via bus technology.
The module is suitable for mounting onto all common DIN rail systems (equipment racks have to be provided by the customer).